The main data sheet of Terminal Strip 
					
					 
					Main technical parameters 
					of Feed-through Terminal block:       
					
					(1)Outshape: 
					
					Processing of sound and 
					drawings of the parts fit, molding no flash, scratches, 
					defects such as miniature
					
					(2) Dimension:  
					
					
					According to Drawing 
					requirement
					
					(3) Insulation 
					resistance: 
					
					DC500V megger test by 
					Road and Road between:> MΩ charged between sites and easy 
					access to parts> MΩ
					
					(4) Withstanding 
					Voltage:  
					
					Test voltage: Road and 
					Road between the site and easy to live between the contact 
					area AC2500V (rated voltage less than 300V,  the test 
					voltage of 2000V), frequency 50HZ, 1 minute without 
					breakdown, flicker,
					
					(5) Cable retention: 
					
					
					The regular insertion of 
					the corresponding nominal connection capacity of the 
					connection, plug-type terminals for 187 each root should be 
					able to withstand force of 78 N over the role of screw 
					fastening type 80N above; pluggable terminals for each root 
					of 250 force should be able to withstand more than the role 
					of 80N, screw-type fastening more than 80 N
					
					(6) Moisture Resistance :
					
					1. Insulation resistance: 
					before the test ≥ 100MΩ; test ≥ 100MΩ 
					
					2. Pressure: baseline: 
					AC2500V/min; test: AC2500V/min (When rated voltage less than 
					300V, in order to 2000V) 
					
					3. Contact resistance : 
					Before the test, ≤ 3mΩ; test ≤ 6mΩ, no insulation damage, no 
					abnormal appearance
					
					(7) Temperature and flame 
					resistance:  
					
					PBT (G = 20% -30%) and 
					phenolic resin (Bakelite): 180 ℃ ± 3 ℃ for 2 hours, without 
					exception, PC temperature resistance: 180 ℃ ± 3 ℃ for 2 
					hours, no abnormal , PBT, Bakelite, and PC Flammability: 
					UL94-V0
					
					(8) Strength test:
					
					Products fell 6 sides 
					were all from a height of 30cm drop to a natural wood 
					surface, strength and the thickness 20mm, look no 
					deformation, fracture phenomenon.
					
					(9) Contact resistance
					
					
					Between the contacts and 
					contact resistance measurement regulations ≤ 3mΩ, durability 
					test ≤ 6mΩ.
					
					(10) Logo: 
					
					Should the main body of 
					the terminal block has the following permanent signs: 
					
					
					a. Rated Voltage (V)   b. 
					Rated current (A) c. Type d. trademarks or factory name
					
					(11) Glow wire test:
					
					
					Test, although there 
					should be no flame or fire but in the 30s after the removal 
					of the hot wire off
					
					(12) Conductive Metal:
					
					with high conductivity of 
					the brass, phosphor bronze, high elastic, nickel-plated 
					surface to be handled. To steel or copper alloy as the raw 
					material, nickel-plated surface to be handled. Conductive 
					parts of the surface anti-corrosion protection layer should 
					be smooth , no glitches, no rust and other defects.
					
					(13) Terminal strength:
					
					
					In the terminal wing to 
					keep the tension increases 150N 1min, terminal on the wing 
					can not unplug from the matrix
					
					(14) PTI:  Terminal 
					blocks insulated base material should be resistant to 
					tracking, anti-tracking index PTI175
					
					(15) Temperature rise:  
					According to the rated current of power tests, the maximum 
					temperature in the 30K the following
					
					(16) Heat resistance:
					
					
					1. Ball pressure test: 
					ball indentation diameter <2mm
					
					2. Insulation resistance: 
					Before the test, ≥ 100MΩ; test ≥ 100MΩ 
					
					3. Pressure: Before the 
					test, AC2500V/min; test AC2500V/min (as rated voltage less 
					than 300V, in order to 2000V) 
					
					4. Contact resistance: 
					Before the test, ≤ 3mΩ; test ≤ 6mΩ
					
					5. without insulation 
					damage, no abnormal appearance
					
					(17) Cold Resistance:
					
					1. Insulation resistance: 
					Before the test, ≥ 100MΩ; test ≥ 100MΩ 
					
					2. Pressure: Before the 
					test, AC2500V/min; test AC2500V/min (When rated voltage less 
					than 300V, in order to 2000V)
					
					3. Contact Resistance: 
					Test former ≤ 3mΩ; test ≤ 6mΩ 
					
					4. without insulation 
					damage, no abnormal appearance
					
					(18) Thermal cycling test
					
					
					1. Insulation resistance: 
					Before the test, ≥ 100MΩ; test ≥ 100MΩ
					
					2. Pressure: Before the 
					test, AC2500V/min; test AC2500V/min (When rated voltage less 
					than 300V, in order to 2000V) 
					
					3. Contact resistance : 
					Before the test, ≤ 3mΩ; test ≤ 6mΩ 
					
					4. without insulation 
					damage, no abnormal appearance